Each conductor that enters and leaves = 1. Conductor terminated inside = 1. All conductors of the same size sharing the same status can be grouped.

Other allowances

Volume used
โ€” cu-in
of โ€” cu-in available

Breakdown

ItemCu-in

Per-conductor volume

AWGCu-in each
#181.50
#161.75
#142.00
#122.25
#102.50
#83.00
#65.00
โšก US / NEC 314.16 only. This calculator uses the NEC 314.16(B) volume-per-conductor method (US National Electrical Code). It is not valid for Canadian installations โ€” CEC 12-3034 uses a different method with different conductor allowances and different device-fill rules, and the numbers do not interchange. Canadian apprentices: use CEC 12-3034 Table 22/23 directly, by hand, for now.

Within US scope: volume is per conductor of a given AWG. Confirm against the box's stamped/marked interior volume โ€” that overrides everything if larger. Boxes for domed covers, plaster rings, and extension rings can add volume โ€” check the manufacturer marking. When in doubt, size up.